J2014001L402-CC SHELF 数据手册
GE
Preliminary Data Sheet
Compact Power Line Shelves
RS485 type shelves for the GP100 rectifier
Model: J2014001L4xx
Features
L401
L401C
L402
L422
Mounts into standard 19” EIA-310-D racks
Terminal block AC connections
-48Vdc output
Adjustable mounting ears
Supports hot-swapping of modules
Mechanical latching slots
RS485 based GE Galaxy Protocol
Emergency Power OFF pin (Interlock)
Passes Zone 4 earthquake requirements
CUR*† recognized
CB report
CE Mark§
Shock & Vibration: Meets IPC 9562 Class II
Description
This Preliminary Data Sheet documents the capabilities of shelves supporting the RS485 based interface. These shelves are
designed for use with the GP100H3R48RE and associated family of rectifiers.
GE offers a comprehensive set of supporting components. A system controller is normally inserted into the first shelf. Normally, the
system controller communicates using the GE Galaxy Protocol. The purpose of the controller is to maintain the functionality of the
power system and inform/be-guided- by remote management controllers. Further information on the capabilities of these turnkey systems can be obtained from your GE Sales Representative
* UL is a registered trademark of Underwriters Laboratories, Inc.
† CSA is a registered trademark of Canadian Standards Association.
§ This product is intended for integration into end-user equipment. All CE marking procedures of end-user equipment should be followed. (The CE mark is placed on
selected products.)
** ISO is a registered trademark of the International Organization of Standards
May 25, 2016
©2016 General Electric Company. All rights reserved.
GE
Preliminary Data Sheet
Compact Power Line Shelves
RS485 type shelves for the GP100 rectifier
Model: J2014001L4xx
Absolute Maximum Ratings
Stresses in excess of the absolute maximum ratings can cause permanent damage to the device. These are absolute stress ratings only, functional
operation of the device is not implied at these or any other conditions in excess of those given in the operations sections of the data sheet. Exposure
to absolute maximum ratings for extended periods can adversely affect the device reliability.
Parameter
Input Voltage: Continuous
Symbol
Min
Max
Unit
VIN
0
600
Vac
TA
-10
751
°C
Tstg
-40
85
°C
2087
VAC
Operating Ambient Temperature
Storage Temperature
I/O Isolation voltage to Frame (100% factory Hi-Pot tested)
Electrical Specifications
Unless otherwise indicated, specifications apply over all operating input voltage, load, and temperature conditions.
INPUT
Symbol
Min
Typ
Max
Unit
Operational Range
Parameter
VIN
320
380/480
530
VAC
Frequency Range
FIN
47
50/60
AC Input Current, (3 - all phases operational)
Recommended AC Breaker Size
IIN
Leakage Current (per , 530VAC, 60Hz)
IIN
Input – Output
Input-Chassis/Signals
Isolation (per EN60950)
10
15
2.5
@ 480VAC
@ 380VAC
63
Hz
15
AAC
AAC
3.5
mA
V
3000
2000
Symbol
Min
Typ
Max
W
0
-
12,000
W
250
ADC
VDC
VAC
VAC
MAIN OUTPUT
Parameter
Output Power
IOUT
V
Max output current
Isolation Output/frame – other circuits
100
Unit
General Specifications
Parameter
Reliability
Min
Typ
Max
TBD
Unpacked Weight
Packed Weight
Units
Hrs
Notes
Full load, 25C ; MTBF per SR232 Reliability protection
for electronic equipment, issue 2, method I, case III,
Kgs/Lbs
TBD
Kgs/Lbs
Safety/Standards Compliance
Safety Standards
UL60950-1, CAN/CSA C22.2 No 60950-1, EN60950-1
Certification Marks
CE mark, UL Recognized (Canada and U.S.)
1
See the derating guidelines published in the rectifier data sheet
May 25, 2016
©2016 General Electric Company. All rights reserved.
Page 2
GE
Preliminary Data Sheet
Compact Power Line Shelves
RS485 type shelves for the GP100 rectifier
Model: J2014001L4xx
Environmental Specifications
Parameter
Min
Typ
Max
Units
Notes
Ambient Temperature
Operating
-10
55
°C
Storage
-40
85
°C
5
95
%
6
Grms
NEBS GR-63-CORE, Level 3, 20 -2000Hz, min 30 minutes
Zone
NEBS GR-63-CORE, all floors, Seismic Zone 4 Designed
and tested to meet NEBS specifications.
Humidity
Shock and Vibration acceleration
Earthquake Rating
4
Relative humidity, non-condensing
Interfacing the L401, L401C shelves
OPTIONAL STRAP
(PROVIDED)
DC OUTPUT
INTERLOCK
L401C ONLY
AC INPUT
AC2
SHELF TO SHELF
SUP GRD
AC1
1.00
5/8
1/4-20 STUDS
3/8-16 NUTS
TORQUE : 240 IN-LBS
BOLTING HARDWARE PROVIDED
Input (L401 and L402)
Wire size: 16 – 10 AWG
Torque: 7 IN-LBS
Min strip length: 3/8 inch
Interlock (L401C only)
Shelf connector: Molex 43020-0200,
suggested mate: Molex 43025-0200
1st L401C
2nd L401C
Nth L401C
To
external
controller
Last shelf
(jumper included)
May 25, 2016
©2016 General Electric Company. All rights reserved.
Page 3
GE
Preliminary Data Sheet
Compact Power Line Shelves
RS485 type shelves for the GP100 rectifier
Model: J2014001L4xx
Shelf-to-shelf (L401 and L402)
Note: Shelf 1 is a L402 shelf with a system controller slot. Jumpers between pins 22-23 are included only on this shelf
Pin
1, 3
4, 6
7, 9
10, 12
13, 15
16, 18
19, 21
22
23
24
May 25, 2016
Signal
rsvd
rsvd
Bay addr
RS485+
RS485L_GND
rsvd
SHID_A
F_VBSHID_C
©2016 General Electric Company. All rights reserved.
Page 4
GE
Preliminary Data Sheet
Compact Power Line Shelves
RS485 type shelves for the GP100 rectifier
Model: J2014001L4xx
Interfacing the L402 shelf
OPTIONAL STRAP
(PROVIDED)
AC INPUT
DC OUTPUT
AC 2
1.00
SHELF TO SHELF
CONTROLLER
.625
AC 1
3PH , 3W + PE
1-WIRE
ETHERNET
RJ45 JACK
3/8-16 NUTS
OPTIONAL
ALARM RELAY INTERFACE
.875
AC CABLE
KNOCKOUT
Shelf-to-shelf (L402 initialization jumper)
Pin
1, 3
4, 6
7, 9
10, 12
13, 15
16, 18
19, 21
22
23
24
Label
rsvd
rsvd
Bay addr
RS485+
RS485L_GND
rsvd
SHID_A
F_VBSHID_C
Jumper
between 22-23
1st shelf only
Shelf_ID components
(all shelves)
1-wire and Ethernet
Pin
1
2
3
4
5
6
7
8
ETHERNET – J2
Signal
VB-
May 25, 2016
1
RS485-
Pin
1
2
3
1 – WIRE - J1
Signal
1-wire
GND
5V
VB+
RS485+
L_GND
©2016 General Electric Company. All rights reserved.
Page 5
GE
Preliminary Data Sheet
Compact Power Line Shelves
RS485 type shelves for the GP100 rectifier
Model: J2014001L4xx
Optional Alarm Relay Interface (J2014001L000A)
The Relay interface is orderable directly from the factory, or it can be installed as an assembly. The interface plugs into the side of
the controller extension board and gets secured by two retention screws as shown below. The pin assignment in the tables below
corresponds to the controller listed in the accessories section. The function of these signals can change when other controllers are
used.
There are a total of 6 output relay contacts, labeled ALM1 through ALM6, accessible via this controller. Functional assignment is
documented in the controller manual. The return for relay 6 is through ALM1C, the return for relay 1.
FBAT is available to interface a battery through an internal PTC to the output (-48V) bus.
BALM3 –BALM6 are connected internally through a resistor and an opto-isolator from each pin to power return. They can be used
to monitor 4 independent battery positions.
For further information review the CC848836981 controller manual.
No. of relays:
Relay contacts
Wire size
Torque
Strip length
6
60V, 0.5A max
28 – 16 AWG
2 in-lb
5/16”
Interface bracket retention screws
Relay interface retention screws:
Pin
TB1-1
TB1-2
TB1-3
TB1-4
TB1-5
TB1-6
TB1-7
TB1-8
TB1-9
TB1-10
Mating to the controller extension board
Signal
ALM1
ALM2
ALM3
ALM4
ALM5
ALM1C
ALM2C
ALM3C
ALM4C
ALM5C
Pin
TB2-1
TB2-2
TB2-3
TB2-4
TB2-5
TB2-6
TB2-7
TB2-8
TB2-9
TB2-10
Signal
BALM6
No connect
BALM3
BALM4
BALM5
FBAT
FBAT
FBAT
ALM6
ALM1C
Controller
The USB port on the front of the controller provides access to a
remote controller that can be used to provide configuration
information to the controller. Review the controller manual for
further information.
May 25, 2016
©2016 General Electric Company. All rights reserved.
Page 6
GE
Preliminary Data Sheet
Compact Power Line Shelves
RS485 type shelves for the GP100 rectifier
Model: J2014001L4xx
Rectifier Installation (all lists)
Caution: The rectifier latch is not a carrying handle
To release the latch press the dark gray area
Slide in the rectifier while the latch is in the open position
As resistance is felt when inserting, slowly close the latch to
complete the insertion. When the latch is locked the rectifier is
positively engaged in its housing.
The rectifier can get extracted or inserted while the bus is hot.
Latch release
The rectifier is keyed to ensure that it gets inserted into the
correct shelf. Do not force mating beyond normally anticipated
resistance in order to avoid permanent damage.
May 25, 2016
©2016 General Electric Company. All rights reserved.
Page 7
GE
Preliminary Data Sheet
Compact Power Line Shelves
RS485 type shelves for the GP100 rectifier
Model: J2014001L4xx
Interfacing L422N shelf
This shelf contains a L402 and a L401 shelf in a single enclosure. This enclosure cannot be expanded.
DC OUTPUT
INTERLOCK
CONTROLLER LAN
(OPTIONAL)
AC INPUIT
DC CABLES MAY EXIT EITHER UP OR DOWN
1.10
3PH , 3W + PE
1/4-20 STUDS
BOLTING HARDWARE PROVIDED
NUETRAL BLOCK
CONNECTION
NOT REQUIRED
ETHERNET
Rj45 JACK
1.85
AC CABLE
KNOCKOUT
1.08
AC CABLE
KNOCKOUT
Input (L401 and L402)
Wire size: 6 AWG max
Torque: 15 IN-LBS
Strip length: 3/8 inch
The neutral conductor is not required
Frame ground terminations
May 25, 2016
©2016 General Electric Company. All rights reserved.
Page 8
GE
Preliminary Data Sheet
Compact Power Line Shelves
RS485 type shelves for the GP100 rectifier
Model: J2014001L4xx
Shelf keying
3
1
The key is a pin positioned in one of six holes on the bottom of the shelf
Below is a view of the rectifier slot filler configured for slot 3
May 25, 2016
©2016 General Electric Company. All rights reserved.
Page 9
GE
Preliminary Data Sheet
Compact Power Line Shelves
RS485 type shelves for the GP100 rectifier
Model: J2014001L4xx
Package Outline
L401, L402
17.60
23.28
21.05
3.00
MTG EARS
MAY BE SHIFTED
BACK IN THIS
INCREMENTS
19.16
18.31
.250
1.25
1.73
May 25, 2016
©2016 General Electric Company. All rights reserved.
Page 10
GE
Preliminary Data Sheet
Compact Power Line Shelves
RS485 type shelves for the GP100 rectifier
Model: J2014001L4xx
L422N
17.60
18.25
3.00
MTG EARS
MAY BE SHIFTED
FORWARD IN THIS
INCREMENTS
5.99
19.16
.25
18.31
3.00
May 25, 2016
©2016 General Electric Company. All rights reserved.
3.4
Page 11
GE
Preliminary Data Sheet
Compact Power Line Shelves
RS485 type shelves for the GP100 rectifier
Model: J2014001L4xx
Ordering Information
Part Number
Description
Comcode
Shelves
J2014001L401
GP100, 3-480, RS485 communications, add-on /stand-alone shelf, configured
for slot 3, hardware and shelf interconnect included
150041780
J2014001L402
GP100, 3-480, RS485 communications, controller slot, LAN, RJ45 terminations,
configured for slot 3
150041781
J2014001L402
GP100, 3-480, RS485 communications, controller slot, LAN, RJ45 terminations,
with L000A alarm relay interface, configured for slot 3, hardware and shelf
interconnect included
150050125
J2014001L422N
GP100, 3-480, RS485 communications, controller slot, RJ45 terminations,
includes a L401 and a L402 shelves in the same enclosure. Hardware included
150048864
Accessories
GCP841A_0I6R
May 25, 2016
GP100 Slot Filler
150045141
Shelf-to-shelf interconnecting cable
850035254
Alarm Relay Interface ( J2014001 L000A )
150050124
Controller equipped with 6 output relays and a USB interface
150043558
©2016 General Electric Company. All rights reserved.
Page 12
GE
Preliminary Data Sheet
Compact Power Line Shelves
RS485 type shelves for the GP100 rectifier
Model: J2014001L4xx
Safety
Product Labeling
Follow all warnings and instructions marked on the product. Some of the safety symbols used with the CP3500 rectifier and this
shelf may include the following. They may also be accompanied by instructions:
Mounting and Installation
• This product shall be installed in compliance with mounting requirements for the ultimate application.
• This product must be installed, serviced, and operated only by skilled and qualified personnel who have the necessary
knowledge and practical experience with electrical equipment and who understand the hazards that can arise when working on
this type of equipment. This product is intended for use in a Restricted Access Location.
• This equipment is to be used in controlled environments (an area where the humidity is maintained at levels that cannot cause
condensation on the equipment, the contaminating dust is controlled, and the steady-state ambient temperature is within the
range specified).
• This equipment has been evaluated for use in a continuous ambient temperature of up to 55°C and the application environment
should not exceed 55°C.
• The CE mark if provided on the product is applied to show conformance to the requirements outlined in the European Union’s
Low Voltage Directive {2006/95/EC} and EMC Directive {2004/108/EC}.
• This shelf has been evaluated for hot swapping.
• A separate protective Earthing terminal is provided at the rear of the shelf
– the building installation shall provide a means for connection to protective earth; and
– the equipment is to be connected to that means; and
– a SERVICE PERSON shall check whether or not the socket-outlet from which the equipment is to be powered provides a
connection to the building protective earth. If not, the SERVICE PERSON shall arrange for the installation of a PROTECTIVE
EARTHING CONDUCTOR from the separate protective Earthing terminal to the protective earth wire in the building.
Output Connections
• All field wiring should comply with the U.S. National Electrical Code (NEC) and/or applicable local codes/standards.
• Routing of the DC output cables should guarantee that cables are not in contact with sources of heat and surfaces that may
damage the cable insulation.
• The DC output is not provided with a fuse or circuit breaker suitable for branch circuit protection. Therefore, the power shelf
should be mounted in the same rack or cabinet as the equipment being powered. Use interconnecting power cables suitable for
the application and sized to carry the rated output current. The interconnecting cables should be capable of carrying the
overload current and short circuit current without damage or risk of fire.
• The output for the system is SELV and has available power greater than 240VA.
• Insulation on output field-wired conductors should be rated no less than 90°C. Wiring internal to enclosed equipment cabinets
should be rated at 105°C (minimum). The provided DC output cords (red and black wires) are rated for 105°C.
• Before opening the insulating cover to gain access to load and ground connections, ensure all power supplies are disconnected
from the AC MAINS.
AC Input Connections
• This shelf is configured with primary internal wiring and Molex connectors, rated for internal factory wiring only. The Molex
connector is not UL Recognized for direct connection to the AC mains. The internal wiring is not UL recognized to be directly
accessible by a user. Consideration should be taken on the end product’s Listing to comply with NEC requirement for AC mains
installations.
AC branch circuits to this equipment must be protected with fuses or circuit breakers sized as required by the U.S. National
Electric Code (NEC) and/or local codes. Up to four AC mains power cords are required to power the shelf (one for each rectifier).
Each power cord should be connected to a separate AC mains branch circuit with an overcurrent protector rated at no more
than 30A.
• The power supply mains inlet may be used as the means to provide AC protective earthing.
• An accessible AC disconnect/protection device to remove AC power from the equipment in the event of an emergency must be
provided. An accessible socket-outlet/receptacle installed near the equipment is also acceptable as a disconnect.
• The equipment is powered by multiple AC inputs (one per rectifier). Disconnect all AC sources of power before servicing.
• These units are to be used with TN-S power systems only.
May 25, 2016
©2016 General Electric Company. All rights reserved.
Page 13
GE
Preliminary Data Sheet
Compact Power Line Shelves
RS485 type shelves for the GP100 rectifier
Model: J2014001L4xx
Safety Symbols and Guidelines
Read and understand all instructions before attempting any installation of this product. When installing, operating, or maintaining
the J85480S1 Power System, basic safety precautions should always be followed to reduce the risk of fire, electric shock, and injury
to persons. Such precautions include the following:
This symbol identifies the need to refer to the equipment instructions for important information.
This symbol identifies the presence of hazardous AC or DC voltages or hazardous energy levels. In the context of
this product
The DC output cables contain electrical energy levels capable of causing heating and arcing if shorted to
metal objects. Make connections with the power disconnected.
Hazardous AC voltage and DC electrical energy is contained within the enclosure of the power shelf. No
user or field serviceable parts inside.
This symbol is used to identify safety earth ground connection points within the equipment.
German Safety Guidelines
Installationsanleitung
• Alle Ausgänge des Gerätes erfüllen die Anforderungen für SELV nach IEC/EN60950-1.
• Die Ausgänge des Gerätes liegen über den Limits für Energiegefahr nach IEC/EN60950-1 (>240 VA). Das Gerät ist zum
Einbau in ein Montage-Rack bestimmt. Siehe Einbaubestimmungen in der Montageanleitung, um eine Gefährdung des
Benutzers während der Installation zu vermeiden.
ACHTUNG:
Hoher Ableitstrom Vor Anschluss an den Versorgungsstromkreis unbedingt Erdungsverbindung herstellen
• Das Produkt ist zum Gebrauch in einer Umgebungstemperatur von max. 55°C bestimmt.
• Die Gerätestecker des Produktes sind dazu bestimmt, eine sichere Erdung des Gerätes herzustellen.
• Das Produkt ist zum Gebrauch in einer Umgebung mit Verschmutzungsgrad 2 nach IEC/EN60950 bestimmt.
• Die Netzteile des Gerätes können während des Betriebes einzeln ausgetauscht werden (Hot Swapping).
• Das Gerät wurde zusammen mit den Anschlussleitungen (ohne Anschlussstecker) geprüft. Die Installation eines Steckers des
jeweiligen Landes, sollte nur durch geschultes Service Personal durchgeführt werden.Als alternative könnte eine Vorinstallation des
Steckers bereits bei der Herstellung erfolgt sein.Hungarian48ggs
Contact Us
For more information, call us at
USA/Canada:
+1 877 546 3243, or +1 972 244 9288
Asia-Pacific:
+86.021.54279977*808
Europe, Middle-East and Africa:
+49.89.878067-280
http://www.geindustrial.com/products/critical-power
GE Critical Power reserves the right to make changes to the product(s) or information contained herein without notice, and no
liability is assumed as a result of their use or application. No rights under any patent accompany the sale of any such product(s)
or information.
May 25, 2016
©2016 General Electric Company. All International rights reserved.
Page 14